| Hauptseite > Publikationsdatenbank > Tenability criteria in performance-based fire safety engineering: practitioner's perspectives from a global survey |
| Journal Article | FZJ-2026-05524 |
; ; ; ; ;
2026
Elsevier
New York, NY [u.a.]
This record in other databases:
Please use a persistent id in citations: doi:10.1016/j.firesaf.2026.104938
Abstract: To improve our understanding on the usage of tenability criteria in Performance Based Fire Safety Engineering, support future research and code development, an online survey was conducted, gathering 254 responses from 43 countries. Visibility in smoke is confirmed as both the most frequently measured (90.1%) and most influential (91.4%) tenability criterion. Temperature shows the largest measurement-versus-influence gap: tracked by 76.5% but governing decisions for only 45.8% of respondents. Toxicity-related criteria remain underused — FED is applied by 22.2% and FEC by fewer than 10% of practitioners, with FED adoption declining among the most experienced engineers (8.4% vs 19.4% among juniors). The C-factor in Jin's visibility model ranges from 3 to 8 in practice, with 30.5% of respondents choosing values on a project-by-project basis and 21% unable to specify their choice. Visibility thresholds span 3 m to 30 m across regions, with 10 m being dominant (from 97% in the UK to 64% in the Americas). Measurement heights range from 1.5 m to 2.5 m, with 2.0 m most common (52.1%) followed by 1.8 m (29.5%). Five-region analysis demonstrates that local regulatory traditions shape criterion selection, threshold values, and measurement methodology as strongly as independent engineering judgement.
|
The record appears in these collections: |