Please use a persistent id in citations: doi:10.1109/SEST67798.2026.11712311
Abstract: Distribution grids are often sparsely monitored, which limits observability and accurate voltage estimation. While traditional state estimation methods rely on pseudo-measurements that can reduce accuracy, most data-driven estimators depend on a specific monitoring configuration. This paper proposes an iterative optimal meter placement strategy for a Correlated Gaussian Process (Corr-GP) voltage estimator. Using spatial voltage correlations to infer unmeasured states via Corr-GP, meter locations are selected based on incremental information gain. As such, near-optimal performance compared to an exhaustive search is achieved while significantly reducing the required computational effort. Tests across multiple operating scenarios and comparisons with a traditional exhaustive approach confirm the robustness and superiority of the proposed method, demonstrating its potential as a practical solution for improving observability in future distribution grids.
|