| Home > Publications database > Lead-acid Batteries and Lithium-ion Batteries in parallel Strings for an Energy Storage System for a Clinic in Africa |
| Book/Proceedings | FZJ-2017-02842 |
2016
Czech Technical University in Prague
ISBN: 978-80-01-05950-0
This record in other databases:
Please use a persistent id in citations: http://hdl.handle.net/2128/14175
Abstract: The aim of this paper is to develop an energy storage system for a clinic in Nioki, Africa. Caused by the difficulties of non existing infrastructure, the clinic needs its own power supply. Therefore, a simulation model combining lead-acid and lithium-ion batteries was developed and validated. The system under observation works with two different battery types in parallel without an energy management system. As input data the model uses weather data and load data. To be able to distribute the current correctly between thetwo batteries, the behaviour for each cell has to be calculated in every time step. A 14-V-system was built to validate the simulation model. The results of the simulation model and the measurement are compared and evaluated by comparison of the voltage and current curves of the batteries. The results show that the curves of the graphs for both, the measured data and the simulated data, are close enough to accept the simulation model as validated for the presented application.
|
The record appears in these collections: |