Operational Validation of a Power Distribution Algorithm for a Modular Megawatt Battery Storage System

 ;  ;  ;  ;

2023
Wiley-VCH Weinheim

Batteries & supercaps 6(3), e202200414 () [10.1002/batt.202200414]

This record in other databases:    

Please use a persistent id in citations: doi:  doi:

Abstract: Large-scale battery storage systems have become popular for various grid services in recent years. A worldwide market growth for battery storage has led to increased competition in several grid service markets. Modular large-scale battery storage systems require a safe, highly available, and intelligent energy management system (EMS) in order to be economically competitive. One component of this EMS is the control for distributing the power requests between individual battery units of the large-scale battery storage system. As the EMS is usually undisclosed intellectual property of the system manufacturers, there is only little information on real-world operation available. To contribute, we present a rule-based power distribution algorithm (SPDA) in this paper and validate it through field tests on a 6 MW/7.5 MWh system that is providing frequency containment reserve to the German power grid. The results show that especially when combining different battery technologies, the SPDA can exploit individual technological strengths. In this way, the state of charge of the batteries, energy throughput and power load of the batteries can be controlled to extend the lifetime. Moreover, the SPDA managed to shift nearly 80 % of the energy throughput to one battery unit to protect less cyclic stable batteries and make use of the advantage of cyclic stable battery technologies, while fulfilling all grid service requirements. By shifting those large quantities of the energy throughput to more cyclic stable battery units, the large-scale battery storage system experienced in sum up to 45 % less cyclic aging with the SPDA than with a symmetrical power distribution algorithm. Furthermore, the operational efficiency of a large-scale battery storage system can be significantly improved via additional software adaptations of the power distribution, depending on the system layout.

Classification:

Note: Zudem unterstützt durch das BMWK Projekt EMMUseBat (FundingCode:03EI4034)

Contributing Institute(s):
  1. Helmholtz-Institut Münster Ionenleiter für Energiespeicher (IEK-12)
Research Program(s):
  1. 1223 - Batteries in Application (POF4-122) (POF4-122)
  2. BMWK-03ESP265F - M5BAT: Modularer multi-Megawatt multi-Technologie Mittelspannungsbatteriespeicher; Teilvorhaben: Entwicklung von Li-Ionen Batterien, Monitoring und Erstellung eines Designhandbuchs (BMWK-03ESP265F) (BMWK-03ESP265F)

Appears in the scientific report 2024
Database coverage:
Medline ; Creative Commons Attribution CC BY 4.0 ; OpenAccess ; Clarivate Analytics Master Journal List ; Current Contents - Physical, Chemical and Earth Sciences ; DEAL Wiley ; Essential Science Indicators ; IF >= 5 ; JCR ; SCOPUS ; Science Citation Index Expanded ; Web of Science Core Collection
Click to display QR Code for this record

The record appears in these collections:
Dokumenttypen > Aufsätze > Zeitschriftenaufsätze
Institutssammlungen > IMD > IMD-4
Workflowsammlungen > Öffentliche Einträge
IEK > IEK-12
Publikationsdatenbank
Open Access

 Datensatz erzeugt am 2024-04-05, letzte Änderung am 2025-02-03


OpenAccess:
Batteries Supercaps - 2022 - Koltermann - Operational Validation of a Power Distribution Algorithm for a Modular Megawatt - Volltext herunterladen PDF
2022_12_16_Leistungsaufteilung - Volltext herunterladen PDF